Skip to main content
Siemens 5SY4325-8FA — 3-Pole MCB (DIN Rail)

Siemens 5SY4325-8FA SENTRON MCB, 25 A, D Curve, 3-Pole, 10 k

MPN5SY4325-8FA

Siemens SENTRON miniature circuit breaker, 5SY4325-8FA, D characteristic, 3-pole, 25 A rated, 10 kA breaking capacity per EN 60898, AC 440 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4325-8FA — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY4325-8FA — Protection
ParameterValue
Tripping characteristic (curve)D
Breaking capacity per EN 6089810 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree3
5SY4325-8FA — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)2.1 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
Rated voltage (AC, single-phase)440 V
5SY4325-8FA — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
Accepts supplementary devicesYes
5SY4325-8FA — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
Vibration resistance (IEC 60068-2-6)±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz

Product details

What it is and what it does

The Siemens SENTRON 5SY4325-8FA is a 3-pole miniature circuit breaker (MCB) with a D tripping characteristic, rated 25 A at 35 °C and breaking 10 kA per EN 60898 at 440 V AC. The D curve means it tolerates high inrush currents — typical for motor, transformer, or welding loads — without nuisance tripping, while still clearing a fault fast enough to protect the downstream cable. It occupies 3 modular width units (54 mm) on a DIN rail and mounts in any position, which simplifies panel layout when space is tight.

Ratings and what they mean for fit

The 25 A rating holds at 35 °C ambient; at 40 °C it derates to 23.8 A, and at 55 °C to 21.88 A. If your panel runs hot — say, inside a crowded enclosure near other heat sources — you need to account for that derating or step up to a higher-rated frame. The 10 kA breaking capacity per EN 60898 is the standard for residential and light commercial distribution boards; for industrial panels with higher available fault current, you'd want to verify the SCCR at the panel level. The 440 V AC rating covers both single-phase and multi-phase operation, so it works across 230/400 V systems common in European and Asian installations.

Integration notes

Mounts on a DIN rail via the quick assembly system — no tools needed for snapping on or off. The combined terminal at top and bottom accepts the same conductor size, so wiring order doesn't matter. Depth is 76 mm (installation depth 70 mm), which fits standard 80 mm deep enclosures. IP20 with connected conductors means it's protected against finger contact but not washdown; keep it inside a sealed panel if the environment is wet or dusty. Pollution degree 3 and overvoltage category III suit it for fixed installations in industrial or commercial buildings.

Frequently asked questions

How do I get current pricing and availability for 5SY4325-8FA?

Submit an RFQ through this listing; we source and quote to order through independent distribution, with availability and current pricing confirmed at quote time.

What is 5SY4325-8FA's listed depth?

The depth is 76 mm, with an installation depth of 70 mm.

What is 5SY4325-8FA's listed width?

The width is 54 mm, which corresponds to 3 modular width units on a DIN rail.

Will 5SY4325-8FA drop into a panel specified around 5SY4316-7CV without rewiring?

Both are 3-pole SENTRON MCBs on the same DIN-rail footprint, so the mechanical fit is identical. The electrical difference is the rating and curve — verify the load current and inrush profile before swapping.

What compliance documentation does Siemens provide for 5SY4325-8FA?

The part is designed to EN 60898 for breaking capacity and carries the SENTRON brand's standard declarations. For specific RoHS, REACH, or UL documentation, request it with your RFQ.

MPN