Skip to main content
Siemens 5SY4332-6CC — 3-Pole MCB (DIN Rail)

Siemens 5SY4332-6CC SENTRON MCB, B-Curve 3-Pole, 10 kA

MPN5SY4332-6CC

Siemens SENTRON miniature circuit breaker, order code 5SY4332-6CC, B-curve, 3-pole, 10 kA breaking capacity per IEC 60898, 400 V AC rated, 3 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4332-6CC — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY4332-6CC — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 6089810 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree3
5SY4332-6CC — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)3.2 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
Rated voltage (AC, single-phase)440 V
5SY4332-6CC — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
Accepts supplementary devicesYes
5SY4332-6CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
Vibration resistance (IEC 60068-2-6)±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz

Product details

What this MCB is and what it does

The Siemens 5SY4332-6CC is a SENTRON miniature circuit breaker with a B tripping characteristic, 3 poles, rated 400 V AC and breaking 10 kA per IEC 60898. The B-curve trips between 3 and 5 times rated current — standard for resistive and general-purpose loads in commercial or light industrial panels where inrush is low. At 400 V AC, the 10 kA breaking capacity means it can safely interrupt a fault current up to that level without upstream cascading, as long as the available fault current at the panel doesn't exceed this. It also carries a UL 1077 / CSA C22.2 No.235 rating of 5 kA, so it's accepted in North American supplementary protection applications. The 3-pole design switches all three phases together; there's no neutral pole switching.

Mounting and integration

Snaps onto DIN rail via the quick assembly system, occupying 3 modular width units (54 mm). Installation depth is 70 mm, overall depth 76 mm. Mounting position is any orientation. The enclosure is IP20 with conductors connected — standard for panel-internal use. Pollution degree 3 and overvoltage category III suit it for fixed installations where transient overvoltages are expected. Combined terminals top and bottom accept wiring without separate busbar adapters. Sealable for tamper-proof applications.

Frequently asked questions

What is 5SY4332-6CC's breaking capacity?

10 kA per IEC 60898 at 400 V AC, and 5 kA per UL 1077 / CSA C22.2 No.235.

Where can I buy 5SY4332-6CC?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 5SY4332-6CC drop into a panel specified for 5SY4140-7?

Both are SENTRON 3-pole MCBs on the same DIN-rail footprint, so mechanical fit is the same. The difference is the tripping curve — 5SY4332-6CC is B-curve, while the 5SY4140-7 is a different characteristic. Verify the curve matches your load type before substituting.

MPN
5SY4332-6CC