Three-pole design (3P) with no neutral switching — fits three-phase loads like small pumps, compressors, or sub-distribution.
Derating and ambient conditions
Rated current drops with temperature: 30.08 A at 40 °C, 29.09 A at 45 °C, 28.03 A at 50 °C, 26.94 A at 55 °C. If the panel runs hot, size the upstream protection accordingly — a 32 A breaker at 55 °C carries only 27 A continuous. IP20 with conductors connected, so it belongs inside a closed enclosure, not in a washdown zone.
Mounting position any, so vertical or horizontal orientation works. Combined terminal top and bottom means the line and load conductors land on the same style of clamp. Sealable for anti-tamper applications. Halogen-free and silicon-free construction suits environments where outgassing is a concern (clean rooms, medical, food processing).