Siemens 5SY4332-7CV — 3-Pole MCB (DIN Rail)

Siemens 5SY4332-7CV MCB, 3P C-Curve 32A 15kA IEC 60947-2

MPN5SY4332-7CV

Siemens 5SY4332-7CV, 3-pole miniature circuit breaker, C-curve, 32 A rated, 15 kA breaking capacity per IEC 60947-2, 3 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4332-7CV — Identification
ParameterValue
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY4332-7CV — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per IEC 60947-215 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree3
5SY4332-7CV — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Power loss per pole at rated current (AC, hot)3.3 W
Neutral conductor switchingNo
5SY4332-7CV — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
Accepts supplementary devicesYes
5SY4332-7CV — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
Vibration resistance (IEC 60068-2-6)±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz

Product details

The Siemens 5SY4332-7CV is a 3-pole miniature circuit breaker (MCB) with a C tripping characteristic, rated 32 A at AC and a breaking capacity of 15 kA per IEC 60947-2.

At 35 °C ambient the breaker carries its full 32 A. At 40 °C it derates to 29.66 A, at 45 °C to 28.42 A, at 50 °C to 27.1 A, and at 55 °C to 25.73 A. The 3-pole unit occupies 3 modular width units (54 mm wide, 90 mm tall, 76 mm deep, 70 mm installation depth) and mounts in any position via the quick-assembly system onto standard DIN rail. IP20 with connected conductors, pollution degree 3, overvoltage category III — it's built for the inside of a control cabinet, not for wet environments.

Frequently asked questions

What is the breaking capacity of the Siemens 5SY4332-7CV?

Engineers must confirm 15 kA interrupting rating matches fault current at the point of installation before purchase.

What does the C-curve mean on a 5SY4332-7CV MCB?

C-curve suitability for inductive loads drives correct breaker selection and prevents nuisance tripping.

Is the Siemens 5SY4332-7CV compliant with IEC 60947-2?

Standards compliance is required for spec approval and panel certification in industrial installations.

What is the difference between the 5SY4332-7CV and the 5SY4332-7CC?

Variant comparison helps buyers confirm they are ordering the correct suffix for their application.