Siemens 5SY4332-8FA — 3-Pole MCB (DIN Rail)

Siemens 5SY4332-8FA SENTRON MCB, 32 A, 3P, D-curve, 10 kA

MPN5SY4332-8FA

Siemens SENTRON 5SY4332-8FA miniature circuit breaker, 3-pole, D-characteristic, 32 A rated, 10 kA breaking capacity at 400 V AC, 3 width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4332-8FA — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Suitability for operationMechanical engineering / industry
5SY4332-8FA — Protection
ParameterValue
Tripping characteristic (curve)D
Breaking capacity per EN 6089810 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
5SY4332-8FA — Electrical
ParameterValue
Rated current (AC)400 V
Rated voltage (AC, multi-phase)440 V
Rated frequency50/60 Hz
5SY4332-8FA — Mechanical
ParameterValue
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY4332-8FA — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

The Siemens 5SY4332-8FA is a SENTRON miniature circuit breaker (MCB) rated 32 A at 400 V AC, with a D tripping characteristic and 10 kA breaking capacity per EN 60898. Three-pole construction (3P) in a 54 mm wide, 3-unit housing. Current-production part — sourced to order against an RFQ.

What the ratings mean for fit

The D-curve (tripping characteristic class D) means the magnetic trip activates at 10–20× rated current — designed for loads with high inrush, like transformers, welding equipment, or motor starters. The 10 kA breaking capacity at 400 V AC (per EN 60898) certifies it can safely interrupt a fault current up to that level without welding contacts or cascading upstream. For a 32 A circuit, that's adequate for most industrial sub-distribution panels where the prospective short-circuit current stays under 10 kA. Wire range accepts 0.75 to 35 mm² solid or stranded — covers everything from control-circuit tails to main feeder conductors. Terminal torque spec is 3.5 N·m with screw-type terminals; combined terminal top and bottom allows through-wiring or daisy-chaining without extra connectors. Halogen-free and silicon-free construction matters for installations in clean rooms, semiconductor fabs, or environments where outgassing during a fault could contaminate optics or sensitive surfaces. IP20 with connected conductors — suitable for enclosed panel mounting, not for wet or dust-exposed locations.

Mounting and integration

Snaps onto DIN rail via the quick-assembly system — standard 35 mm rail. Mounting position any; installation depth 70 mm plus the 76 mm overall depth leaves clearance for wiring behind the panel door. Sealable cover option (yes) allows lockout/tagout compliance per site safety procedures.

Frequently asked questions

What is the breaking capacity of 5SY4332-8FA?

10 kA at 400 V AC per EN 60898. That is the standard industrial distribution rating for this class — sufficient for most sub-panels where the prospective fault current is below that threshold.

What wire sizes does 5SY4332-8FA accept?

Solid or stranded conductors from 0.75 mm² up to 35 mm². The screw terminals are rated for 3.5 N·m torque.

Where can I buy 5SY4332-8FA?

Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
5SY4332-8FA