Siemens 5SY4340-6 — 3-Pole MCB (DIN Rail)

Siemens 5SY4340-6 SENTRON MCB, 3P B-Curve 40A, 10kA

MPN5SY4340-6
Active

Siemens SENTRON 5SY4340-6, 3-pole miniature circuit breaker, B-curve, 40 A rated, 10 kA (EN 60898-1) / 15 kA (IEC 60947-2), 3 MW units wide, IP20, current production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4340-6 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY4340-6 — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 6089810 kA
Breaking capacity per IEC 60947-215 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree3
5SY4340-6 — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)3.6 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
Rated voltage (AC, single-phase)440 V
5SY4340-6 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
Accepts supplementary devicesYes
5SY4340-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
Vibration resistance (IEC 60068-2-6)±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz

Product details

The 5SY4340-6 is a 3-pole SENTRON miniature circuit breaker rated 40 A at 35 °C with a B tripping characteristic — meaning it trips at 3–5× rated current, suited for resistive and general-purpose loads where short-circuit protection is needed without nuisance trips from moderate inrush. Breaking capacity is 10 kA per IEC/EN 60898-1 and 15 kA per IEC 60947-2 / UL1077 — the higher figure under 60947-2 applies when the breaker is used in industrial distribution rather than final-circuit residential/commercial; that dual rating gives the specifier one part for both duty classes. Temperature derating is published per degree: 38.42 A at 40 °C, 37.6 A at 45 °C, 36.76 A at 50 °C, 35.92 A at 55 °C, 35.04 A at 60 °C — if the panel ambient runs above 35 °C, the actual load limit drops; size the downstream load against the derated figure, not the 40 A nameplate.

Occupies 3 modular width units (54 mm) on DIN rail, depth 76 mm, installation depth 70 mm — fits standard 3-MW cutouts; the quick-assembly fastening method means it snaps onto the rail without tools and releases via a screwdriver slot.

Approvals cover IEC/EN 60898-1, IEC/EN 60947-2, and UL1077 — accepted in European, UKCA, and North American industrial panels; halogen-free and silicon-free construction meets clean-environment specs for semiconductor or food-grade zones.

Frequently asked questions

How do I get current pricing and availability for 5SY4340-6?

Submit an RFQ through this listing; availability and current pricing are confirmed at quote time through independent distribution channels.

What compliance documentation does Siemens provide for 5SY4340-6?

The breaker carries IEC/EN 60898-1, IEC/EN 60947-2, and UL1077 approvals; it is halogen-free and silicon-free per the manufacturer's declaration.

What is the temperature derating for 5SY4340-6 above 35 °C?

Rated current drops to 38.42 A at 40 °C, 37.6 A at 45 °C, 36.76 A at 50 °C, 35.92 A at 55 °C, and 35.04 A at 60 °C — size the continuous load against the derated value for the actual panel ambient.