What the 15 kA Icu rating means for panel coordination
Provided the upstream transformer and cable impedances keep the fault level under that 15 kA figure, this breaker holds selectivity with a suitably rated upstream device — no cascading failure into the bus.
Snap-on DIN rail mounting per EN 60715. The 3-pole footprint occupies three modular widths (17.5 mm per pole). Terminals accept copper conductors up to 25 mm², which is adequate for the 40 A rating on a 400 V three-phase circuit feeding a distribution sub-board or a motor control centre feeder.