Skip to main content
Siemens 5SY4340-6KK11 — 3-Pole MCB (DIN Rail)

Siemens 5SY4340-6KK11 SENTRON MCB, 3P 40A B-curve, 10/15kA

MPN5SY4340-6KK11

Siemens SENTRON 5SY4340-6KK11, miniature circuit breaker, 3-pole, 40 A, B characteristic, 10 kA per EN 60898, 15 kA per IEC 60947-2, for railway applications.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4340-6KK11 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Suitability for operationMechanical engineering / industry
5SY4340-6KK11 — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 6089810 kA
Breaking capacity per IEC 60947-215 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree3
5SY4340-6KK11 — Electrical
ParameterValue
Rated current (AC)40 A
Rated voltage (AC, multi-phase)440 V
5SY4340-6KK11 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
5SY4340-6KK11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

At 35 °C ambient the breaker carries the full 40 A. At 40 °C it derates to 38.4 A, at 50 °C to 36.76 A, and at 60 °C to 35.04 A. That means in a crowded enclosure with multiple breakers side by side, the actual permissible load current is lower than the nameplate 40 A — size the downstream load for the ambient your panel sees, not the 35 °C figure.

The combined terminal at top and bottom accepts both busbar and conductor connections — no need to remove the busbar to land a wire.

Frequently asked questions

What are the key ratings for 5SY4340-6KK11?

Three-pole, 40 A, B-curve miniature circuit breaker with 10 kA breaking capacity per EN 60898 and 15 kA per IEC 60947-2. The higher 15 kA figure governs for industrial panel SCCR calculations.

How do I get pricing and availability for 5SY4340-6KK11?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and confirmed availability — stock levels and lead times vary and are confirmed at quote time.

Will 5SY4340-6KK11 drop into a panel specified around 5SY4304-7CV?

The 5SY4340-6KK11 shares the same SENTRON 5SY family footprint — 3 modular widths (54 mm), 76 mm depth, DIN-rail snap-on. It will physically fit the same panel location, but the 5SY4304-7CV is a different rating (lower current, different curve); verify the branch-circuit protection requirements before substituting.

What compliance documentation is available for 5SY4340-6KK11?

The breaker carries EN 60898 and IEC 60947-2 ratings, is halogen-free and silicon-free, and is designed for railway applications. Standard Siemens SENTRON declaration of conformity and material compliance (RoHS, REACH) are available on request.

MPN
5SY4340-6KK11