Siemens 5SY4340-7KK11 — 3-Pole MCB (DIN Rail)

Siemens 5SY4340-7KK11 SENTRON MCB, 3P 40A C-Curve 10kA

MPN5SY4340-7KK11

Siemens SENTRON 5SY4340-7KK11, 3-pole miniature circuit breaker, 40 A rated current, C tripping characteristic, 10 kA per EN 60898 / 15 kA per IEC 60947-2, 400 V AC, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4340-7KK11 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Suitability for operationMechanical engineering / industry
5SY4340-7KK11 — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 6089810 kA
Breaking capacity per IEC 60947-215 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
5SY4340-7KK11 — Electrical
ParameterValue
Rated current (AC)400 V
Rated voltage (AC, multi-phase)440 V
Rated frequency50/60 Hz
5SY4340-7KK11 — Mechanical
ParameterValue
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY4340-7KK11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

It breaks 10 kA per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC, which covers most industrial panel fault levels. The 3-pole, 3-width-unit (54 mm) body snaps onto the DIN rail with the quick-assembly system and accepts conductors from 0.75 up to 35 mm² solid or stranded, so it handles both control-circuit tails and feeder-size cable on the same terminal.

Two breaking-capacity ratings are listed because the standard under which the fault is tested changes the result: 10 kA under EN 60898 (the domestic / light-commercial benchmark) and 15 kA under IEC 60947-2 (the industrial standard that also tests for coordination with upstream devices).

Mounts in any position on the DIN rail. The 54 mm width (3 width units at 18 mm each) and 76 mm depth (70 mm installation depth behind the panel face) fit standard SENTRON cut-outs. Combined terminals top and bottom mean the same box lug accepts solid or stranded copper from 0.75 mm² up to 35 mm² — no adapter needed when stepping from a 4 mm² control wire to a 25 mm² feeder. Sealable for lockout/tagout compliance. Overvoltage category III suits fixed-installation distribution boards.

Frequently asked questions

Where can I buy 5SY4340-7KK11 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is 5SY4340-7KK11's breaking capacity?

It is rated 10 kA per EN 60898 and 15 kA per IEC 60947-2 at 400 V AC. The higher figure governs industrial panel SCCR coordination.

What wire sizes does 5SY4340-7KK11 accept?

The terminals accept solid or stranded copper from 0.75 mm² up to 35 mm² — a wide range that covers both small control wires and larger feeder cables.

Will 5SY4340-7KK11 drop into a panel specified around 5SY6613-8 without rewiring?

Both are SENTRON MCBs on the same DIN-rail footprint, so the mechanical fit is identical. The key difference is rating: 5SY4340-7KK11 is a 40 A C-curve, while 5SY6613-8 is a different current/trip combination — verify the load requirement before swapping.

What compliance documentation does Siemens provide for 5SY4340-7KK11?

The part carries a railway-design classification, halogen-free and silicon-free declarations, and IP20 touch protection. Standard Siemens documentation includes the CE declaration, IEC/EN test certificates, and material compliance data — request these with the RFQ.