Skip to main content
Siemens 5SY4350-6KK11 — 3-Pole MCB (DIN Rail)

Siemens 5SY4350-6KK11 SENTRON MCB, 3P B-Curve, 10/15kA

MPN5SY4350-6KK11

Siemens SENTRON 5SY4350-6KK11, 3-pole B-curve miniature circuit breaker, 10 kA (EN 60898-1) / 15 kA (IEC 60947-2), 400 V AC, 54 mm wide, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

5SY4350-6KK11 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry

Protection

5SY4350-6KK11 — Protection
ParameterValue
Tripping characteristic (curve)B
Breaking capacity per EN 6089810 kA
Breaking capacity per IEC 60947-215 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree3

Electrical

5SY4350-6KK11 — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)4.3 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
Rated voltage (AC, single-phase)440 V

Mechanical

5SY4350-6KK11 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
Accepts supplementary devicesYes

Environmental

5SY4350-6KK11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
Vibration resistance (IEC 60068-2-6)±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz

Product details

The Siemens SENTRON 5SY4350-6KK11 is a 3-pole miniature circuit breaker with a B tripping characteristic, rated 10 kA interrupting capacity per EN 60898-1 and 15 kA per IEC 60947-2 at 400 V AC. The B-curve trips between 3 and 5 times rated current — standard for protecting residential or light commercial cable runs where inrush is low (lighting, socket circuits). The dual rating means it meets both the domestic-standard (EN 60898-1) and industrial-standard (IEC 60947-2) SCCR requirements, giving it flexibility for panel builds that need to satisfy either code.

Integration & Fit

Snap-on DIN rail mount, 3 MW (modular width units) at 54 mm wide. Depth 76 mm, installation depth 70 mm. Combined top and bottom terminals accept feed from either direction. Sealable cover option (yes) for tamper-proof installations. Operating temperature range -40 to 75 °C, with derated humidity limits above 55 °C. IP20 with conductors connected — panel interior only, not field-exposed.

Frequently asked questions

Where can I buy the 5SY4350-6KK11 and get a price?

This part is available to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

What are the key interrupting ratings for this MCB?

10 kA per EN 60898-1 and 15 kA per IEC 60947-2 at 400 V AC. The higher IEC rating covers industrial panel SCCR requirements.

MPN
5SY4350-6KK11