The D curve holds through motor inrush (typically 10–20× rated current for a few cycles) so you don't nuisance-trip on a compressor or conveyor start.
Rated 63 A at 35 °C, it derates to 59.98 A at 40 °C and 56.83 A at 50 °C — so if your panel ambient runs 45 °C, plan for 58.4 A continuous load. The 3-pole design (3P) switches all three phases together; no neutral pole built in, so it's for a 3-wire delta or a 4-wire wye where the neutral is separately protected.