Skip to main content
Siemens 5SY4380-7 — 3-Pole MCB (DIN Rail)

Siemens 5SY4380-7 SENTRON MCB, 3P C-Curve, 10kA

MPN5SY4380-7
Active

Siemens SENTRON 5SY4380-7, 3-pole C-curve miniature circuit breaker, 10 kA breaking capacity per EN 60898, 15 kA DC per IEC 60947-2, for 400 V AC / 60 V DC operation.

$93.98Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4380-7 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY4380-7 — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 6089810 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree3
5SY4380-7 — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)6.7 W
Mechanical service life (operating cycles, typ.)10 000
Neutral conductor switchingNo
Rated voltage (AC, single-phase)440 V
5SY4380-7 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
Accepts supplementary devicesYes
5SY4380-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
Vibration resistance (IEC 60068-2-6)±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz

Product details

Breaking capacity and duty class

The Siemens 5SY4380-7 is a 3-pole, C-curve miniature circuit breaker from the SENTRON series, rated 10 kA breaking capacity at 400 V AC per EN 60898 and 15 kA at DC per IEC 60947-2. The C-curve trips at 5–10× rated current, making it suited for mixed resistive and inductive loads in control panels. The DC rating of 15 kA at 60 V (max 72 V) covers DC auxiliary circuits common in switchgear and automation cabinets.

Mounting and environmental range

Compliance and production status

Certified to IEC/EN 60898-1 and IEC/EN 60947-2; also to UL/CSA standards with 5 kA breaking capacity for North American installations. Halogen-free and silicon-free construction supports clean-room and sensitive-environment installations.

Frequently asked questions

What are the physical dimensions?

Depth 76 mm, width 54 mm (3 modular units), height 90 mm.

MPN
5SY4380-7