80 A C-Curve MCB for Distribution Panels
Rated 80 A at 35 °C ambient, the breaker derates to 76.24 A at 40 °C, 74.24 A at 45 °C, 72.24 A at 50 °C, and 70.16 A at 55 °C — a thermal curve that matters when the panel is sealed or near heat sources. The 3-pole design (3P) switches all phases; neutral is not switched.
Operating temperature range from -40 °C to 75 °C, with humidity limits of 95% up to 55 °C, 55% up to 70 °C, and 35% up to 75 °C. The product designation per EN 61346-2 and IEC 81346-2 is F (protective device).