Skip to main content
Siemens 5SY4408-8CC — 4-Pole MCB (DIN Rail)

Siemens 5SY4408-8CC SENTRON MCB, 4P D-curve 8 A, 10 kA

MPN5SY4408-8CC

Siemens SENTRON 5SY4408-8CC miniature circuit breaker, 4-pole, D tripping characteristic, 8 A rated current, 10 kA breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4408-8CC — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4408-8CC — Ratings
ParameterValue
Number of poles4
Rated current (In), AC8 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
5SY4408-8CC — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 6089810 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Touch protectionYes
5SY4408-8CC — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4408-8CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY4408-8CC — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

What this MCB is and what the ratings mean

The Siemens 5SY4408-8CC is a 4-pole miniature circuit breaker from the SENTRON 5SY series, designed for DIN-rail mounting in distribution boards and control panels. Its D tripping characteristic means it tolerates the high inrush currents typical of motor loads, transformers, and discharge lighting — the magnetic trip threshold sits at 10–20× rated current, so nuisance tripping on startup is avoided. Rated 8 A at AC and 10 kA breaking capacity per EN 60898, it handles fault currents up to that level without cascading upstream. The 4-pole construction switches all three phases plus neutral; note the neutral is not switched separately — the breaker opens all poles together.

Temperature derating and installation notes

Rated current is temperature-sensitive: at 40 °C ambient the continuous rating drops to 7.52 A, at 50 °C to 7.01 A, and at 55 °C to 6.74 A. If the panel runs hot, factor the derating into the load schedule. The breaker occupies 4 modular width units on a DIN rail, with a quick-assembly fastening system and any mounting position. Installation depth is 70 mm. IP20 with connected conductors — standard for enclosed distribution boards; not rated for washdown. Pollution degree 3 suits industrial environments with conductive dust or condensation.

Frequently asked questions

Where can I buy 5SY4408-8CC and how do I get a price?

The 5SY4408-8CC is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing.

Will 5SY4408-8CC drop into a panel specified around 5SY7210-7CC without rewiring?

Both are 4-pole SENTRON MCBs with the same modular width (4 MUs) and DIN-rail mounting, so physical fit is the same. The key difference is the tripping characteristic: 5SY4408-8CC is D-curve (10–20× In, for motor/transformer loads), while 5SY7210-7CC uses a different curve — check that the protective coordination still matches the downstream load before swapping.

What compliance documentation does this brand provide for 5SY4408-8CC?

The 5SY4408-8CC is certified to IEC/EN 60898 (10 kA breaking capacity) and carries UL 1077 / CSA C22.2 No. 235 recognition (5 kA interrupting rating). The SENTRON series typically includes CE marking and manufacturer declarations for RoHS/REACH compliance.

MPN
5SY4408-8CC