Skip to main content
Siemens 5SY4410-6 — 4-Pole MCB (DIN Rail)

Siemens 5SY4410-6 SENTRON MCB, 4P 10A B-Curve, 10/20 kA

MPN5SY4410-6
Active

Siemens SENTRON 5SY4410-6, miniature circuit breaker, 4-pole, 10 A, B characteristic, 10 kA (IEC 60898-1) / 20 kA (IEC 60947-2).

$341.20Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4410-6 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4410-6 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated voltage, AC (multi-phase)440 V
5SY4410-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
5SY4410-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4410-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY4410-6 — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)1.3 W

Product details

Selection Notes

Depth behind the panel is 70 mm (76 mm overall).

Marked as current production. The part carries IEC/EN 60898-1 and IEC/EN 60947-2 approval with UL1077 recognition. Halogen-free and silicon-free construction; neutral conductor is not switched on this 4-pole variant.

Frequently asked questions

What is the listed depth of the 5SY4410-6?

The overall depth is 76 mm; installation depth behind the panel face is 70 mm.

What is the width of the 5SY4410-6?

Width is 72 mm, which corresponds to 4 modular units on a DIN rail.

Will the 5SY4410-6 drop into a panel specified around the 5SY4350-8 without rewiring?

Yes, because both breakers share the same 4-module footprint and mounting system. No wiring changes are needed as long as the current rating and trip curve of the 5SY4410-6 are suitable for your circuit.

What compliance documentation does Siemens provide for the 5SY4410-6?

The breaker complies with IEC/EN 60898-1, IEC/EN 60947-2, and UL1077. It is halogen-free and silicon-free, and it is sealable. RoHS and REACH statements are available from the manufacturer.

MPN