What this MCB carries and where
Breaking capacity is 10 kA per EN 60898 and 20 kA per IEC 60947-2; at DC (72 V) the interrupting rating is 15 kA per IEC 60947-2. For UL 1077 / CSA C22.2 No. 235 the AC rating is 5 kA. Energy limiting class 3 means the breaker clears a fault fast enough to let downstream equipment ride through a limited let-through energy — important for coordinating with downstream contactors or drives that have lower short-circuit withstand.
The housing occupies 4 width units (72 mm wide) and the total depth including terminals is 76 mm. With IP20 protection (with connected conductors) and overvoltage category III, it is suited for enclosure-mounted distribution boards in mechanical engineering and industrial environments. Touch protection is built into the design.