Skip to main content
Siemens 5SY4413-6 — 4-Pole MCB (DIN Rail)

Siemens 5SY4413-6 SENTRON 4-Pole MCB, 13 A, B Curve

MPN5SY4413-6
Active

Siemens SENTRON 5SY4413-6, 4-pole miniature circuit breaker, 13 A rated current, B tripping characteristic, 10 kA (EN 60898) / 20 kA (IEC 60947-2) breaking capacity, 4 modular width units, depth 76 mm.

$318.99Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4413-6 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4413-6 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC13 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
5SY4413-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
5SY4413-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4413-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY4413-6 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

The 5SY4413-6 snaps onto a standard DIN rail via the quick assembly system, occupying 4 modular width units (72 mm) with a depth of 76 mm and an installation depth of 70 mm.

Rated 13 A at AC with a B tripping characteristic, the 5SY4413-6 delivers a breaking capacity of 10 kA per EN 60898-1 and 20 kA per IEC 60947-2 / UL1077 — the higher figure applies when the MCB is certified as a supplementary protector under UL 1077. The 20 kA rating per IEC 60947-2 gives selectivity headroom against downstream faults in industrial panel feeders, while the 10 kA per EN 60898-1 covers residential and commercial branch circuits.

Rated 13 A at 35 °C ambient, the continuous current derates to 11.39 A at 60 °C — a 12% drop that must be factored into panel thermal budgets. The operating ambient range spans -40 °C to 75 °C, with the surrounding humidity limited to 95% up to 55 °C, 55% up to 70 °C, and 35% up to 75 °C.

Frequently asked questions

Where can I buy the Siemens 5SY4413-6 and get a price?

The 5SY4413-6 is sourced to order against an RFQ through independent distribution channels.

What is the breaking capacity of Siemens 5SY4413-6?

The breaking capacity is 10 kA per EN 60898-1 and 20 kA per IEC 60947-2 / UL1077, depending on the applicable standard for the installation.

MPN