Skip to main content
Siemens 5SY4413-7 — 4-Pole MCB (DIN Rail)

Siemens 5SY4413-7 4-Pole MCB, C-Curve

MPN5SY4413-7
Active

Siemens SENTRON 5SY4413-7, 4-pole miniature circuit breaker, C characteristic, 10 kA (EN 60898) / 20 kA (IEC 60947-2), 400 V AC, 4 MW.

$338.66Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4413-7 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4413-7 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated voltage, AC (multi-phase)440 V
5SY4413-7 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
5SY4413-7 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4413-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY4413-7 — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)1.4 W

Product details

The Siemens 5SY4413-7 is a 4-pole SENTRON miniature circuit breaker with a C tripping characteristic, rated 10 kA per EN 60898-1 and 20 kA per IEC 60947-2 at 400 V AC. That 20 kA figure under 60947-2 gives selectivity headroom in industrial panelboards where fault currents can exceed the domestic 10 kA ceiling — the breaker clears without upstream devices needing to trip.

DC suitability and voltage limits

Yes, the 5SY4413-7 is suitable for DC applications. The rated DC voltage is 60 V, with a maximum operating voltage of 72 V DC. This makes it usable in DC distribution boards, battery circuits, or control power supplies where 4-pole isolation is needed.

Certifications and environmental range

Certified to IEC / EN 60898-1, IEC / EN 60947-2, and UL 1077 — the UL 1077 rating is 5 kA. Ambient temperature range spans -40 °C to 75 °C, with derating above 55 °C per the humidity limits (95% RH up to 55 °C, 55% RH up to 70 °C, 35% RH up to 75 °C). Halogen-free and silicon-free construction.

Mounting position any orientation. Quick assembly system for snapping onto the rail. Sealable — allows locking in the ON position for lockout/tagout. IP20 with conductors connected.

Frequently asked questions

What is the breaking capacity of Siemens 5SY4413-7?

Design engineers need this to confirm compatibility with fault current levels in the installation.

Is 5SY4413-7 suitable for DC applications and what is the DC voltage rating?

Maintenance techs and engineers need to know if it can be used in DC circuits; specs show 60V DC rated.

What certifications does Siemens 5SY4413-7 have?

Compliance with IEC/EN and UL1077 is critical for project acceptance and safety standards.

Where can I buy Siemens 5SY4413-7 and what is the current price?

Sourcing buyers need immediate price and stock to fill a BOM or procure for maintenance.

What is the equivalent replacement for 5SY4413-7 from other brands?

Brokers and buyers facing supply constraints need cross-reference options to complete orders.

What is the depth of 5SY4413-7 and does it fit standard DIN rail enclosures?

Physical fit in existing panels is a top concern for replacement and new installations.

MPN
5SY4413-7