Skip to main content
Siemens 5SY4415-8 — 4-Pole MCB (DIN Rail)

Siemens 5SY4415-8 4-Pole MCB, D Characteristic, 1.6 A

MPN5SY4415-8
Active

Siemens SENTRON 5SY4415-8, 4-pole miniature circuit breaker, D characteristic, rated 1.6 A AC, 10 kA breaking capacity per EN 60898, 35 kA per IEC 60947-2, 4 MW wide, IP20.

$341.20Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4415-8 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4415-8 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC1.6 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Voltage typeAC
5SY4415-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 6089810 kA
Rated breaking capacity, per IEC 60947-235 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes
5SY4415-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4415-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

The 5SY4415-8: At 1.6 A, the magnetic trip threshold sits between 16 A and 32 A.

Thermal derating and ambient envelope

Rated current holds at 1.6 A up to 35 °C ambient, then derates linearly to 1.4 A at 60 °C. In a sealed, uncooled enclosure the effective continuous load should be budgeted against the 60 °C column unless the panel temperature is verified lower.

Frequently asked questions

What is the breaking capacity of Siemens 5SY4415-8?

The IEC rating allows installation in industrial panels with higher prospective fault current than the EN rating alone covers.

MPN