Siemens 5SY4425-7KK11 — 4-Pole MCB (DIN Rail)

Siemens 5SY4425-7KK11 SENTRON MCB, 4P C-Curve 25 A, 10 kA

MPN5SY4425-7KK11

Siemens SENTRON 5SY4425-7KK11, 4-pole miniature circuit breaker, C-curve, 25 A rated current at AC, 10 kA breaking capacity per EN 60898, 20 kA per IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4425-7KK11 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4425-7KK11 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC25 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Voltage typeAC
5SY4425-7KK11 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity (Icn), per EN 6089810 kA
Rated breaking capacity, per IEC 60947-220 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes
5SY4425-7KK11 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4425-7KK11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

Panel fit and mounting

Snaps onto DIN rail via the quick assembly system, mounts in any position. Occupies 4 modular width units — roughly 72 mm wide — so plan for 4 TE on the rail. Installation depth is 70 mm, overall depth 76 mm. Combined top and bottom terminals accept incoming and outgoing wiring from either end. Sealable for tamper-proofing after commissioning.

Frequently asked questions

Where can I buy 5SY4425-7KK11 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request with quantity and delivery needs; availability and current pricing are confirmed at quote time.

Will 5SY4425-7KK11 drop into a panel specified for 5SY4304-7CV?

Both are 4-pole SENTRON MCBs on the same DIN-rail footprint, so mechanical fit is identical. The key difference is rating: 5SY4425-7KK11 is a 25 A C-curve, while 5SY4304-7CV is a lower-current variant (exact rating not in this evidence). Verify the load current and trip curve match before swapping — the rail space and wiring terminals are compatible.

What compliance documentation does Siemens provide for 5SY4425-7KK11?

The breaker is halogen-free and silicon-free. It carries ratings per EN 60898 (10 kA) and IEC 60947-2 (20 kA), and is classified per IEC 81346-2 and DIN EN 61346-2 as function F. Standard Siemens documentation includes CE declaration of conformity and product-specific test certificates — request these with the RFQ.

MPN