Skip to main content
Siemens 5SY4440-7KK11 — 4-Pole MCB (DIN Rail)

Siemens 5SY4440-7KK11 SENTRON MCB, 4P C-Curve 40 A, 10/15 kA

MPN5SY4440-7KK11

Siemens SENTRON 5SY4440-7KK11, 4-pole miniature circuit breaker, C-curve, 40 A rated current, 10 kA / 15 kA breaking capacity, 76 x 72 x 90 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4440-7KK11 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4440-7KK11 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC40 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
5SY4440-7KK11 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
5SY4440-7KK11 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4440-7KK11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY4440-7KK11 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

What this 4-pole C-curve 40 A MCB is built for

The Siemens SENTRON 5SY4440-7KK11 is a 4-pole miniature circuit breaker with a C tripping characteristic rated at 40 A at 35 °C (38.4 A at 40 °C, 36.76 A at 50 °C — derate accordingly). It's designed for mechanical engineering and industrial panel applications, built to DIN EN 60898-1 and also rated under IEC 60947-2 with a 15 kA breaking capacity (10 kA under EN 60898-1). The C-curve (tripping characteristic class C) means it holds up to 5–10× rated current for short periods before tripping magnetically — typical for motor circuits, transformers, and lighting banks where inrush is moderate. At 40 A, that's 200–400 A magnetic trip threshold.

The quick assembly system (fastening method) lets it snap onto the rail without tools. Installation depth is 70 mm, and the mounting position can be any orientation. Sealable design (yes) means you can lock the toggle in position with a padlock — useful for lockout/tagout on a panel door.

Halogen-free and silicon-free construction for applications sensitive to outgassing (railway, marine, clean manufacturing). The product is also designated for railway applications per the design field. The breaking capacity of 15 kA per IEC 60947-2 gives headroom for high-fault panels; the 10 kA per EN 60898-1 is the residential/commercial rating path.

Frequently asked questions

Where can I buy 5SY4440-7KK11 and what's the price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer.

Will 5SY4440-7KK11 drop into a panel specified around 5SY4140-7 without rewiring?

No — the 5SY4140-7 is 1-pole (1 modular width), while the 5SY4440-7KK11 is 4-pole (4 modular widths). The panel would need a different DIN-rail layout and wiring scheme. Use the 4-pole version if the original spec called for a 4-pole breaker.

What compliance documentation does this breaker carry?

It's certified to DIN EN 60898-1 and IEC 60947-2. The product is halogen-free and silicon-free. For specific RoHS/REACH/UL documentation, the manufacturer provides compliance declarations on request.

MPN
5SY4440-7KK11