It sits in the SENTRON family, the standard modular protection range for industrial and commercial panel builds. Breaking capacity is 10 kA per EN 60898 and 15 kA per IEC 60947-2 — the higher figure applies when the breaker is specified under the industrial standard, giving you a safety margin for fault currents up to 15 kA at the panel's supply side.
The B-curve means the magnetic trip activates at 3–5× rated current — so 189–315 A instantaneous trip. Current derating is published across the ambient range: 63 A at 35 °C, 59.98 A at 40 °C, 58.4 A at 45 °C, 56.83 A at 50 °C, 55.12 A at 55 °C, and 53.42 A at 60 °C. If your panel ambient runs above 40 °C, the 40 °C figure (59.98 A) is the one to use for sizing — not the 35 °C headline. Four poles in a 72 mm wide housing — 4 modular-width units.
Rated for mechanical engineering and industry, snaps onto a DIN rail via quick-assembly system, mountable in any position. Installation depth is 70 mm. IP20 with connected conductors — that's the usual protection for inside a panel. The terminals are combined top and bottom, meaning you can feed from either direction, and the supply cord can enter from any position. Touch protection is built in.
Halogen-free and silicon-free construction, plus sealable — useful for environments where outgassing or tampering is a concern.