Rated 10 kA breaking capacity per EN 60898 at 230 V AC, and 5 kA per UL 1077 / CSA C22.2 No.235 — the UL number tells you it's listed as a supplementary protector in North American panels, not a branch-circuit primary breaker, so check your local code classification before specifying. The 1P+N construction (2-pole, one protected pole plus switched neutral) means it isolates both line and neutral when tripped, which matters for single-phase subcircuits where you want full disconnection — common in European distribution boards and industrial control panels.
Dimensions, mounting, and integration
Mountable in any position, IP20 with connected conductors — fine inside a sealed panel, not for wet washdown zones.
Environmental range and compliance
Ambient temperature range from -40 °C to +75 °C, with humidity derating above 55 °C — max 95% RH at 55 °C, dropping to 35% at 75 °C. That's wide enough for unheated plant rooms or outdoor cabinets in most climates. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — survives the shake of a conveyor line or compressor skid.