Siemens 5SY4501-7CV — 1-Pole MCB (DIN Rail)

Siemens 5SY4501-7CV 2-Pole MCB, C-Curve 1A, 15kA IEC 60947-2

MPN5SY4501-7CV

Siemens 5SY4501-7CV, 2-pole miniature circuit breaker, C tripping characteristic, 1A rated current, 15 kA breaking capacity per IEC 60947-2, 36 mm width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4501-7CV — Identification
ParameterValue
Number of poles2
Application suitabilityMechanical engineering / industry
5SY4501-7CV — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY4501-7CV — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4501-7CV — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY4501-7CV is a 2-pole miniature circuit breaker with a C tripping characteristic, rated 1 A at 35 °C per IEC 60947-2. The C-curve (5–10× In) means it handles moderate inrush without nuisance tripping — typical for motor-starter, lighting, and small-transformer circuits where the start-up surge sits below 10 A. Thermal derating is built in: the breaker carries its full 1 A only up to 35 °C. At 40 °C it derates to 0.93 A, at 45 °C to 0.89 A, at 50 °C to 0.8 A, and at 55 °C to 0.8 A. The 2-pole form factor (36 mm wide, 2 modular-width units) switches both phase and neutral — the neutral conductor switching feature is integrated, so no separate neutral block is needed downstream.

Environmental and compliance specs

Rated for ambient temperatures from -40 °C to 75 °C, with humidity limits of 95% RH up to 55 °C, then derating to 35% RH at 75 °C. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — suitable for installation on machine-mounted sub-panels subject to moderate vibration. Sealable terminals and touch protection are standard. These make it a clean fit for food-and-bev, pharmaceutical, or semiconductor-adjacent panels where outgassing or contamination is a concern.

Frequently asked questions

Where can I buy 5SY4501-7CV and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 5SY4501-7CV?

15 kA at 400 V AC per IEC 60947-2. That is the rated ultimate short-circuit breaking capacity (Icu) for this 2-pole C-curve breaker.

What does the C-curve mean on this breaker?

The C tripping characteristic (5–10× In) means magnetic trip occurs between 5 A and 10 A for the 1 A rated version. It is designed for circuits with moderate inrush — motor starters, lighting groups, small transformers — where a B-curve would nuisance-trip on startup.

Will 5SY4501-7CV fit in a panel designed for 5SY4140-7?

Both are 2-pole, 36 mm wide (2 MW) Siemens 5SY-series MCBs sharing the same DIN-rail footprint, terminal layout, and 70 mm installation depth. The 5SY4501-7CV drops into the same panel position without rewiring — the difference is the current rating (1 A vs 40 A for the 5SY4140-7) and the tripping curve (C vs B).

What compliance documentation is available for 5SY4501-7CV?

The breaker is certified to IEC / EN 60947-2, carries CE marking, and is halogen-free and silicon-free. RoHS and REACH declarations are standard with the manufacturer's documentation package for active-production parts.

MPN
5SY4501-7CV