Skip to main content
Siemens 5SY4501-8 — 2-Pole MCB (DIN Rail)

Siemens 5SY4501-8 SENTRON MCB, 2-pole D-curve, 1 A, 10/35 kA

MPN5SY4501-8
Active

Siemens SENTRON 5SY4501-8 miniature circuit breaker, 2-pole, D tripping characteristic, 1 A rated at 35 °C, 10 kA (EN 60898) / 35 kA (IEC 60947-2).

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

5SY4501-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry

Electrical

5SY4501-8 — Electrical
ParameterValue
Number of poles2

Protection

5SY4501-8 — Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII

Mechanical

5SY4501-8 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors

Environmental

5SY4501-8 — Environmental
ParameterValue
Pollution degree3

Product details

Siemens 5SY4501-8 — 2-pole D-curve MCB, 1 A, industrial breaking capacity

The Siemens 5SY4501-8 is a 2-pole miniature circuit breaker from the SENTRON range, with a D tripping characteristic and a rated current of 1 A at 35 °C. It delivers a breaking capacity of 10 kA per EN 60898 and 35 kA per IEC 60947-2 — the higher figure applies when the breaker is used in industrial distribution per the latter standard, giving real headroom for fault-current coordination in a panel. At 400 V AC the 35 kA SCCR means it can interrupt a fault up to that level without upstream devices needing to clear it first; that matters for selectivity studies on a motor control centre or sub-distribution board. The D curve (10–20× In trip) suits loads with high inrush, like small transformers, solenoid banks, or motor starters. Rated current derates with ambient temperature: 0.95 A at 40 °C, 0.9 A at 50 °C, and 0.85 A at 60 °C — so if the panel runs hot, size up one step. The breaker is rated for pollution degree 3 and overvoltage category III, which is the standard for fixed-installation distribution in industrial environments. It mounts in any position on a DIN rail (2 modular width units, 36 mm wide), with a depth of 76 mm and an installation depth of 70 mm. The quick-assembly fastening system and combined top/bottom terminals simplify panel wiring.

Sourcing and lifecycle

The 5SY4501-8 is an active, current-production part. Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

Frequently asked questions

Where can I buy 5SY4501-8 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 5SY4501-8?

10 kA per EN 60898 and 35 kA per IEC 60947-2 at 230/400 V AC. At DC per IEC 60947-2 it is rated 15 kA; under UL 1077 / CSA C22.2 No.235 it is 5 kA.

Will 5SY4501-8 drop into a panel specified around 5SY4301-7CV?

Both are 2-pole SENTRON MCBs with the same width (36 mm) and mounting position (any), so they share the same DIN-rail footprint and terminal layout. The 5SY4301-7CV is a C-curve variant; the D-curve 5SY4501-8 is the direct functional swap for loads with higher inrush. No rewiring needed.

MPN
5SY4501-8