Skip to main content
Siemens 5SY4516-8 — 1-Pole MCB (DIN Rail)

Siemens 5SY4516-8 SENTRON MCB, D Curve, 2-Pole, 10 kA

MPN5SY4516-8
Active

Siemens SENTRON miniature circuit breaker, 5SY4516-8, D characteristic, 2-pole (1P+N), 10 kA (EN 60898) / 20 kA (IEC 60947-2), 230 V AC, 60 V DC, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4516-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityMechanical engineering / industry
5SY4516-8 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY4516-8 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY4516-8 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SY4516-8 is a SENTRON miniature circuit breaker with a D tripping characteristic, 2-pole design (1P+N), and a breaking capacity of 10 kA per EN 60898 or 20 kA per IEC 60947-2 at 230 V AC. It also carries a 15 kA DC rating per IEC 60947-2 at 60 V DC, and 5 kA per UL 1077. The neutral pole switches, so it's suitable for single-phase final circuits where you want to isolate both conductors.

Fit and Mounting

Sourcing and Documentation

For compliance documentation, the manufacturer provides the usual IEC/EN 60898-1 and IEC/EN 60947-2 declarations, plus UL 1077 and CSA C22.2 No. 235 certifications — all standard for this SENTRON series.

Frequently asked questions

What are the key ratings for 5SY4516-8?

Breaking capacity is 10 kA per EN 60898, 20 kA per IEC 60947-2 at 230 V AC, and 15 kA DC at 60 V DC. Tripping characteristic is D, poles are 2 (1P+N), and operating voltage is 230 V AC / 60 V DC.

Will 5SY4516-8 drop into a panel specified around 5SY4116-7CV without rewiring?

Both are 2-pole SENTRON MCBs with the same DIN-rail footprint and 36 mm width, so mechanical fit is identical. The key difference is the tripping curve — 5SY4516-8 is D curve (high inrush), while 5SY4116-7CV is B curve (general purpose). If the panel was wired for a B-curve load profile, swapping to a D curve may change protection coordination; verify the load type before substitution.

Where can I buy 5SY4516-8 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

MPN
5SY4516-8