Skip to main content
Siemens 5SY4563-8 — 1-Pole MCB (DIN Rail)

Siemens 5SY4563-8 SENTRON MCB, 63 A, D Curve, 2-Pole

MPN5SY4563-8
Active

Siemens SENTRON 5SY4 series miniature circuit breaker, 63 A, D characteristic, 2-pole (1P+N), 10 kA per EN 60898, 15 kA per IEC 60947-2, 230 V AC, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4563-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Application suitabilityMechanical engineering / industry
5SY4563-8 — Electrical & Protection
ParameterValue
Tripping characteristic classD
Rated value (EN 60898)10 kA
Overvoltage categoryIII
5SY4563-8 — Mounting & Connection
ParameterValue
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
SealableYes
5SY4563-8 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

What this 63 A D-curve MCB is for

The Siemens 5SY4563-8 is a SENTRON miniature circuit breaker rated 63 A at 230 V AC, with a D tripping characteristic and 2 poles configured as 1P+N. For UL 1077 / CSA C22.2 No. 235 installations, the interrupting rating is 5 kA.

Snaps onto DIN rail via the quick-assembly system — 36 mm wide (2 width units), 90 mm tall, 76 mm deep, with an installation depth of 70 mm.

Frequently asked questions

What conductor sizes does the 5SY4563-8 terminal accept?

Both solid and stranded conductors from 0.75 mm² up to 35 mm². The combined top and bottom terminals handle that range without adapters.

Will 5SY4563-8 drop into a panel that was specified around 5SY3132-6 without rewiring?

Both are SENTRON 5SY-series MCBs with the same 36 mm width, DIN-rail mounting, and terminal ranges, so the physical footprint and wiring are identical. The difference is electrical: the 5SY4563-8 is a 63 A D-curve 1P+N breaker, while the 5SY3132-6 is a different rating and characteristic. Check the downstream load and coordination study before swapping.

MPN
5SY4563-8