Siemens 5SY4602-8CC — SENTRON 4-pole D-curve MCB
It breaks fault currents up to 10 kA per EN 60898 at 400 V AC, and 5 kA per UL 1077 / CSA C22.2 No.235. The unit mounts on a DIN rail via the quick-assembly system, occupies 4 width units (72 mm), and accepts conductors from 0.75 to 35 mm² solid or stranded. Combined terminals top and bottom simplify daisy-chaining. Torque the screw terminals to 2.5–3.5 N·m. Rated for 400 V AC, overvoltage category III, with touch protection and sealable. Ambient range -25 to +55 °C; storage -40 to +75 °C. Halogen-free and silicon-free construction suits clean environments like food processing or semiconductor support areas.
The 5SY4602-8CC carries a current production lifecycle status. No official successor has been issued — this is the active variant. Compliance documentation includes RoHS, REACH, and the relevant IEC/EN/UL/CSA standards. The breaker is certified per EN 60898 (10 kA) and UL 1077 / CSA C22.2 No.235 (5 kA), covering both IEC and North American installations.
Integration & wiring
The neutral pole is switched, not just solidly linked. Mounting position any; installation depth 70 mm (device depth 76 mm). The D-curve 2 A rating is sized for small motor or transformer branch circuits where inrush can exceed 10× rated current for a few cycles.