Siemens 5SY4604-8 — 4-Pole MCB (DIN Rail)

Siemens SENTRON 5SY4604-8 MCB, 4 A D-Curve 4-Pole, 10 kA

MPN5SY4604-8
Active

Siemens SENTRON 5SY4604-8, miniature circuit breaker, 4-pole (3P+N), 4 A rated, D tripping characteristic, 10 kA (EN 60898) / 35 kA (IEC 60947-2) breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4604-8 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4604-8 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC4 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Voltage typeAC
5SY4604-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 6089810 kA
Rated breaking capacity, per IEC 60947-235 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY4604-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4604-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

What this 4 A D-curve MCB is for

The Siemens SENTRON 5SY4604-8 is a 4-pole (3P+N) miniature circuit breaker rated 4 A with a D tripping characteristic, designed for protecting circuits against overloads and short circuits in industrial control panels and mechanical engineering applications. The D-curve means it tolerates high inrush currents — typically used for motor, transformer, or welding equipment circuits where the startup surge would nuisance-trip a B or C curve breaker. The 4 A rating at 35 °C is the base; at elevated panel temperatures it derates to 3.71 A at 45 °C, 3.61 A at 50 °C, 3.5 A at 55 °C, and 3.39 A at 60 °C, so factor the ambient inside your enclosure when sizing.

Breaking capacity and ratings

Rated breaking capacity is 10 kA per EN 60898, which covers most commercial and light industrial distribution boards. For industrial applications where fault currents are higher, the IEC 60947-2 rating of 35 kA applies — that's the number to use when the breaker is specified into a machine control panel with a high-capacity transformer upstream. DC breaking capacity is 15 kA per IEC 60947-2, covering battery-backed or rectifier-fed circuits.

Mounting and integration

Snaps onto DIN rail via the quick assembly system, occupies 4 modular width units (72 mm wide). Mounting position is any, so it fits vertical or horizontal busbar arrangements. Installation depth is 70 mm behind the panel surface; overall depth is 76 mm. Combined terminals top and bottom accept the same conductor range — no special order for feed direction. Touch protection is built in, pollution degree 3 (conductive pollution typical in industrial enclosures).

Frequently asked questions

Where can I buy 5SY4604-8 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for this order code.

What is 5SY4604-8's listed depth (76 mm) on this component line?

Overall depth is 76 mm; installation depth behind the panel face is 70 mm.

What compliance documentation does Siemens provide for 5SY4604-8?

The breaker carries approvals per EN 60898 and IEC 60947-2 for breaking capacity ratings. It is halogen-free and silicon-free, with an IP20 protection class (with connected conductors). Specific RoHS/REACH/UL declarations are part of the standard SENTRON documentation package available on request.

MPN
5SY4604-8