Skip to main content
Siemens 5SY4605-8CC11 — 4-Pole MCB (DIN Rail)

Siemens 5SY4605-8CC11 SENTRON MCB, 4P D 0.5A 10kA

MPN5SY4605-8CC11

Siemens SENTRON 5SY4605-8CC11, 4-pole miniature circuit breaker, D tripping characteristic, 0.5 A rated current, 10 kA breaking capacity per EN 60898, 400 V AC, 4 width units (72 mm).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4605-8CC11 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4605-8CC11 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC400 V
Rated current (In), AC0.5 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Rated voltage, DC (max.)72 V
Voltage typeAC
Rated frequency50/60 Hz
5SY4605-8CC11 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 6089810 kA
Overvoltage categoryIII
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY4605-8CC11 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY4605-8CC11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY4605-8CC11 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

The Siemens 5SY4605-8CC11 is a 4-pole (3P+N) miniature circuit breaker from the SENTRON series, designed for 400 V AC systems with a D tripping curve and a 0.5 A rated current. Rated 400 V AC phase-to-phase, 440 V AC multi-phase, max 72 V DC. 4 width units (72 mm wide).

Termination and wiring constraints

Sourcing and procurement posture

Current-production Siemens SENTRON MCB.

Frequently asked questions

What conductor sizes does 5SY4605-8CC11 accept?

Solid and stranded conductors from 0.75 mm² up to 35 mm². The combined box terminals at top and bottom handle both fine-stranded and solid wire.

Will 5SY4605-8CC11 drop into a panel specified around 5SY7140-8CC?

Both are 4-pole SENTRON MCBs on the same DIN-rail footprint, but the 5SY4605-8CC11 is a D-curve 0.5 A device while the 5SY7140-8CC is a different rating and characteristic. Verify the tripping curve and ampacity match your branch circuit before substituting — the mechanical fit is the same, but the protection coordination may differ.

MPN