Skip to main content
Siemens 5SY4613-5

Siemens 5SY4613-5 SENTRON MCB, 4P, 13 A, Char. A, 10/20 kA

MPN 5SY4613-5
Active

Siemens SENTRON 5SY4613-5, 4-pole (3P+N) miniature circuit breaker, 13 A rated current, tripping characteristic A, 10 kA breaking capacity per EN 60898, 20 kA per IEC 60947-2, IP20, 4 MW.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY4613-5 specifications
ParameterValue
Poles4
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width72 mm
Height90 mm

Product details

Integrator's note on the 5SY4613-5

The Siemens 5SY4613-5 is a 4-pole (3P+N) SENTRON miniature circuit breaker rated at 13 A with a tripping characteristic A. This means the magnetic trip operates at 2 to 3 times In, making it suitable for protecting semiconductor loads or long cable runs where inrush is minimal — not for standard motor starting. The 10 kA breaking capacity per EN 60898 covers domestic/commercial fault levels, while the 20 kA per IEC 60947-2 gives you headroom for industrial panel SCCR requirements. The 4 MW (72 mm) footprint is standard for a 4-pole MCB on a DIN rail.

Thermal derating and environment

Rated 13 A at 35 °C ambient, the 5SY4613-5 derates to 12.48 A at 40 °C, 12.22 A at 45 °C, 11.95 A at 50 °C, 11.67 A at 55 °C, and 11.39 A at 60 °C. If your panel runs hot — say 50 °C inside the enclosure — you lose about 1 A of headroom. The operating range spans -40 °C to 75 °C, with humidity limits of 95% up to 55 °C, tapering to 35% at 75 °C. Pollution degree 3 (conductive pollution) means it's rated for industrial environments, not clean office air.

Panel integration and compliance

Mounts in any position on a DIN rail via the quick assembly system. Installation depth is 70 mm; overall depth 76 mm. Combined terminals top and bottom accept conductors without separate busbar connectors. Touch protection is built in. The part is halogen-free and silicon-free — relevant if the panel is in a clean room or semiconductor fab where outgassing matters. Overvoltage category III means it's rated for fixed installation downstream of the main distribution board. IP20 with connected conductors — fine inside a closed panel, not for wet locations.

MPN
5SY4613-5