Siemens 5SY4615-8 SENTRON MCB, 4P D-1.6A, 10kA EN

MPN5SY4615-8
Active

Siemens SENTRON 5SY4 series, 4-pole miniature circuit breaker, D tripping characteristic, 1.6 A rated current, 10 kA breaking capacity per EN 60898, 35 kA per IEC 60947-2, 400 V AC, 72 V DC max.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4615-8 — Identification
ParameterValue
Type / order code5SY4
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4615-8 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC400 V
Rated current (In), AC1.6 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Rated voltage, DC (max.)72 V
Voltage typeAC
Rated frequency50/60 Hz
5SY4615-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 6089810 kA
Rated breaking capacity, per IEC 60947-235 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY4615-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY4615-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY4615-8 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

Siemens 5SY4615-8 — SENTRON 4-Pole D-Curve MCB, 1.6 A

The Siemens 5SY4615-8 is a SENTRON 5SY4-series miniature circuit breaker with four poles configured as 3P+N, a D tripping characteristic, and a 1.6 A rated current at 400 V AC. It breaks fault currents up to 10 kA per EN 60898 and 35 kA per IEC 60947-2, with a DC rating of 15 kA per IEC 60947-2 and 5 kA per UL 1077 / CSA C22.2 No. 235. Rated for 400 V AC phase-to-phase and 72 V DC maximum, this breaker suits industrial control panels, machinery disconnects, and distribution sub-feeds.

Breaking Capacity & Selectivity

The dual breaking-capacity rating is the key differentiator here: 10 kA under EN 60898 (the domestic / light commercial standard) and 35 kA under IEC 60947-2 (the industrial standard). That 35 kA IEC rating gives headroom for high-fault installations — substation secondaries, large motor control centers, or panelboards with upstream transformers above 500 kVA. The UL 1077 supplementary-protector rating of 5 kA means it's accepted in North American panels as branch-circuit protection for dedicated loads, not as a service disconnect.

Installation & Wiring

Mounts via the quick-assembly system (DIN rail 35 mm) in any position — horizontal, vertical, or upside-down — with an installation depth of 70 mm and overall dimensions 72 mm wide × 90 mm high × 76 mm deep. The 4-pole body occupies 4 width units (72 mm) on the rail. Touch protection meets IP20 with connected conductors.

Humidity tolerance: max 95% RH at 55 °C, derating to 55% at 70 °C and 35% at 75 °C. Halogen-free and silicon-free construction suits clean-room, food-processing, or marine environments where outgassing must be minimized. Approvals include EN 60898, IEC 60947-2, UL 1077, and CSA C22.2 No. 235, covering installations across Europe, North America, and most global markets. The product designation (F per DIN EN 61346-2 / 81346-2) aligns with standard protection-device labeling in panel schematics.

Frequently asked questions

What wire sizes does the 5SY4615-8 accept?

Solid or stranded copper from 0.75 mm² up to 35 mm². Combined top and bottom terminals allow through-wiring.

MPN