Siemens 5SY4615-8

Siemens 5SY4615-8 SENTRON MCB, 4P D-1.6A, 10kA EN

MPN 5SY4615-8
Active

Siemens SENTRON 5SY4 series, 4-pole miniature circuit breaker, D tripping characteristic, 1.6 A rated current, 10 kA breaking capacity per EN 60898, 35 kA per IEC 60947-2, 400 V AC, 72 V DC max.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY4615-8 specifications
ParameterValue
Poles4
IP ratingIP20
MountingQuick assembly system
Temp operating max70 °C
Temp operating min-40 °C
Depth76 mm
Width72 mm
Height90 mm

Product details

Siemens 5SY4615-8 — SENTRON 4-Pole D-Curve MCB, 1.6 A

The Siemens 5SY4615-8 is a SENTRON 5SY4-series miniature circuit breaker with four poles configured as 3P+N, a D tripping characteristic, and a 1.6 A rated current at 400 V AC. It breaks fault currents up to 10 kA per EN 60898 and 35 kA per IEC 60947-2, with a DC rating of 15 kA per IEC 60947-2 and 5 kA per UL 1077 / CSA C22.2 No. 235. Rated for 400 V AC phase-to-phase and 72 V DC maximum, this breaker suits industrial control panels, machinery disconnects, and distribution sub-feeds.

Breaking Capacity & Selectivity

The dual breaking-capacity rating is the key differentiator here: 10 kA under EN 60898 (the domestic / light commercial standard) and 35 kA under IEC 60947-2 (the industrial standard). That 35 kA IEC rating gives headroom for high-fault installations — substation secondaries, large motor control centers, or panelboards with upstream transformers above 500 kVA. The UL 1077 supplementary-protector rating of 5 kA means it's accepted in North American panels as branch-circuit protection for dedicated loads, not as a service disconnect.

Installation & Wiring

Mounts via the quick-assembly system (DIN rail 35 mm) in any position — horizontal, vertical, or upside-down — with an installation depth of 70 mm and overall dimensions 72 mm wide × 90 mm high × 76 mm deep. The 4-pole body occupies 4 width units (72 mm) on the rail. Touch protection meets IP20 with connected conductors.

Humidity tolerance: max 95% RH at 55 °C, derating to 55% at 70 °C and 35% at 75 °C. Halogen-free and silicon-free construction suits clean-room, food-processing, or marine environments where outgassing must be minimized. Approvals include EN 60898, IEC 60947-2, UL 1077, and CSA C22.2 No. 235, covering installations across Europe, North America, and most global markets. The product designation (F per DIN EN 61346-2 / 81346-2) aligns with standard protection-device labeling in panel schematics.