Skip to main content
Siemens 5SY4616-5 — 4-Pole MCB (DIN Rail)

Siemens 5SY4616-5 SENTRON MCB, 4-Pole 16A, Char A, 10/20kA

MPN5SY4616-5
Active

Siemens SENTRON, miniature circuit breaker, 5SY4616-5, 4-pole (3P+N), 16 A at 35 °C, tripping characteristic A, 10 kA (EN 60898) / 20 kA (IEC 60947-2), 50/60 Hz, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4616-5 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4616-5 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC16 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Voltage typeAC
5SY4616-5 — Protection
ParameterValue
Tripping characteristic (trip curve)A
Rated breaking capacity (Icn), per EN 6089810 kA
Rated breaking capacity, per IEC 60947-220 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY4616-5 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4616-5 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

For a panel-builder or site engineer: characteristic A trips between 2 and 3 times rated current, so it's suited for protecting semiconductor loads or long cable runs where standard B or C curves would nuisance-trip on inrush. The 4-pole (3P+N) configuration covers three-phase circuits with a switched neutral, common in industrial distribution panels feeding mixed loads. Ambient temperature derating is built into the spec: at 40 °C the continuous rating drops to 15.36 A, at 50 °C to 14.7 A, and at 60 °C to 14.02 A. In a hot-strip mill or near furnace zones where ambient runs 55 °C, the effective rating is 14.37 A — a real constraint when sizing branch circuits for motor control centers or drive auxiliaries.

Compliance documentation is available from the brand for RoHS, REACH, and the relevant IEC/EN standards (EN 60898, IEC 60947-2). The part carries IP20 protection with connected conductors, so it requires enclosure in a panel or distribution board rated for the environment.

Snap-on mounting to DIN rail, any position. The 72 mm width occupies 4 modular units (each 18 mm), so it fits standard 4-MU cutouts in distribution boards. Sealable cover is standard, which matters for lockout/tagout or meter-sealing requirements.

Frequently asked questions

Where can I buy the 5SY4616-5 and get a price?

The 5SY4616-5 is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the 5SY4616-5's tripping characteristic and what loads is it for?

Tripping characteristic A means the breaker trips at 2 to 3 times rated current. It is designed for protecting semiconductor circuits, long cable runs, or loads with minimal inrush where a B or C curve would nuisance-trip.

What are the key ratings of the 5SY4616-5?

4-pole (3P+N), 16 A at 35 °C, tripping characteristic A, 10 kA breaking capacity per EN 60898 and 20 kA per IEC 60947-2, 50/60 Hz, IP20 with connected conductors.

MPN
5SY4616-5