Siemens 5SY4616-7CC11 — 4-Pole MCB (DIN Rail)

Siemens 5SY4616-7CC11 SENTRON MCB, 4P C-16A 10kA, 400V AC

MPN5SY4616-7CC11

Siemens SENTRON miniature circuit breaker, 5SY4616-7CC11, 4-pole (3P+N), C-curve, 16 A, 10 kA breaking capacity at 400 V AC, 4 MWUs wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4616-7CC11 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4616-7CC11 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC400 V
Rated current (In), AC16 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Rated voltage, DC (max.)72 V
Voltage typeAC
Rated frequency50/60 Hz
5SY4616-7CC11 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity (Icn), per EN 6089810 kA
Overvoltage categoryIII
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY4616-7CC11 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY4616-7CC11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY4616-7CC11 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

Designed for railway applications per the product designation, it also carries an overvoltage category III rating — suitable for fixed-installation distribution boards where transient overvoltages are expected.

Mounts via the quick assembly system — snap-on to DIN rail, any position. At 72 mm wide (4 width units) and 76 mm deep (70 mm installation depth), it occupies standard panel space. The combined terminal top and bottom accept solid or stranded conductors from 0.75 to 35 mm²; tightening torque is 2.5 to 3.5 N·m.

Environmental and operational range

Halogen-free and silicon-free construction. Humidity tolerance: max 95% at 55 °C, derating to 55% at 70 °C and 35% at 75 °C. Neutral conductor switching is built in — no external link needed for the N pole.

Frequently asked questions

Who supplies 5SY4616-7CC11 and how is it quoted for volume purchases?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What is 5SY4616-7CC11's listed depth?

The total depth is 76 mm; installation depth is 70 mm.

What conductor sizes does 5SY4616-7CC11 accept?

Solid or stranded conductors from 0.75 to 35 mm².

Will 5SY4616-7CC11 drop into a panel specified around 5SY3132-6 without rewiring?

No — 5SY3132-6 is a 2-pole MCB with a different pole count and footprint. The 4-pole (3P+N) 5SY4616-7CC11 is wider (72 mm vs. 36 mm for a 2-pole) and requires a different DIN-rail allocation. Rewiring is necessary.

MPN