Siemens 5SY4620-7 SENTRON 4P C-curve MCB
Breaking capacity is 10 kA per EN 60898 and 20 kA per IEC 60947-2, with a DC rating of 15 kA per IEC 60947-2. The C-curve means it trips at 5-10x rated current — standard for general-purpose distribution and moderate motor inrush. Rated current derates with ambient temperature: 20 A at 35 °C, 18.54 A at 45 °C, 18.04 A at 50 °C, 17.5 A at 55 °C, 16.96 A at 60 °C. Use the 45 °C or 50 °C figure when the panel runs warm.
Snap-on mounting to DIN rail, any position. IP20 protection with connected conductors. Degree of pollution 3, overvoltage category III. Sealable, halogen-free, silicon-free. Touch protection fitted. Ambient operating range -40 °C to 75 °C, with humidity limits: max 95% up to 55 °C, max 55% up to 70 °C, max 35% at 75 °C. Suitability marked for mechanical engineering / industry.