Skip to main content
Siemens 5SY4625-5 — Miniature Circuit Breakers (MCB)

Siemens 5SY4625-5 SENTRON MCB, 4-Pole, 25 A, Characteristic

MPN5SY4625-5
Active

Siemens SENTRON miniature circuit breaker, 5SY4625-5, 4-pole (3P+N), 25 A, characteristic A, 10 kA per EN 60898, 20 kA per IEC 60947-2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SY4625-5 — Ratings
ParameterValue
Overvoltage categoryIII
5SY4625-5 — Mechanical
ParameterValue
Width72 mm
Height90 mm
Depth76 mm

Product details

Characteristic A trips between 2 and 3 times rated current — it's the fastest standard curve, meant for protecting semiconductor circuits or long cable runs where you need to clear a fault before the electronics cook. The 4-pole (3P+N) configuration switches all three phases plus the neutral, which is required in TN-S or TT systems where you need to isolate the neutral on a fault. Rated current derates with ambient temperature: 25 A at 35 °C, 24 A at 40 °C, 23.5 A at 45 °C, 22.98 A at 50 °C, 22.45 A at 55 °C, 21.9 A at 60 °C. If your panel runs hot, size the load accordingly — don't count on the full 25 A above 35 °C. Sealable for lockout/tagout compliance.

Frequently asked questions

What is 5SY4625-5's depth?

The depth is 76 mm, with an installation depth of 70 mm. Width is 72 mm (4 modular units), height 90 mm.

MPN
5SY4625-5