Skip to main content
Siemens 5SY4632-6 — 4-Pole MCB (DIN Rail)

Siemens 5SY4632-6 SENTRON MCB, 4P B-Char, 10kA IEC

MPN5SY4632-6
Active

Siemens SENTRON 5SY4632-6, 4-pole miniature circuit breaker, B tripping characteristic, 10 kA (IEC 60898) / 20 kA (IEC 60947-2), 400 V AC, 4 MW, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4632-6 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4632-6 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated voltage, AC (multi-phase)440 V
5SY4632-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
5SY4632-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4632-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY4632-6 — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)2.6 W

Product details

It is not sized for motor-starting inrush; that calls for a C or D curve. At 400 V AC (phase-to-phase) the 20 kA figure gives headroom for high-fault industrial supplies; the 5 kA UL 1077 / CSA 22.2 No. 235 rating covers North American acceptance on branch circuits.

Certified to IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 / CSA 22.2 No. 235, so it carries the documentation a maintenance technician needs for panel acceptance: the dual standard listing covers both European and North American compliance scopes in a single part number.

Snap-on DIN-rail mount, any position. The quick-assembly system and combined top/bottom terminals speed wiring in multi-pole panels. Sealable with a lead seal for metering or safety isolation circuits. Ambient range -40 °C to 75 °C covers most indoor and sheltered outdoor enclosures; humidity derating applies above 55 °C (max 95% RH to 55 °C, dropping to 35% at 75 °C).

Frequently asked questions

What is the breaking capacity of 5SY4632-6?

10 kA per IEC 60898-1, 20 kA per IEC 60947-2 at 400 V AC, and 5 kA per UL 1077 / CSA 22.2 No. 235.

Will 5SY4632-6 drop into a panel specified for 5SY4140-7?

Both are 4-module-width SENTRON MCBs on the same DIN-rail footprint, so the mechanical fit is identical. The difference is in the tripping curve and rating — verify the B-curve and current rating match your branch circuit before substituting.

What compliance documentation does Siemens provide for 5SY4632-6?

The part carries IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 / CSA 22.2 No. 235 certifications. It is halogen-free and silicon-free.

How do I get current pricing and availability for 5SY4632-6?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

MPN