Siemens 5SY4650-6 — 4-Pole MCB (DIN Rail)

Siemens 5SY4650-6 SENTRON MCB, 50 A, B Curve, 4-Pole

MPN5SY4650-6
Active

Siemens SENTRON 5SY4650-6, 4-pole (3P+N) miniature circuit breaker, B characteristic, 50 A rated current, 10 kA (EN 60898) / 15 kA (IEC 60947-2) breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4650-6 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4650-6 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC50 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
5SY4650-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Rated breaking capacity (Icn), per EN 6089810 kA
Rated breaking capacity, per IEC 60947-215 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Touch protectionYes
5SY4650-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4650-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY4650-6 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

50 A B-curve MCB for distribution and machine panels

The 3P+N design switches all three phases and switches the neutral, which matters for TN-S or TN-C-S systems where neutral isolation is required during maintenance or fault clearing.

Thermal derating and ambient conditions

The 50 A rating holds at 35 °C ambient. At 45 °C it derates to 47 A, at 50 °C to 45.95 A, at 55 °C to 44.9 A, and at 60 °C to 43.8 A. If the panel runs hot — say 50 °C inside the enclosure — the breaker's continuous current capability drops by about 8%, so the connected load must be sized accordingly. IP20 with connected conductors is standard for panel-mounted breakers; the enclosure provides the overall IP rating.

Halogen-free and silicon-free construction matters in clean environments — semiconductor fabs, battery lines, or food processing areas where outgassing from a fault could contaminate product or sensitive electronics. The touch-protected terminals reduce the risk of accidental contact during panel maintenance.

Frequently asked questions

Will 5SY4650-6 drop into a panel specified around 5SY4304-7CV without rewiring?

Both are 4-pole SENTRON MCBs on the same DIN-rail footprint, so the mechanical fit is the same. The key difference is the current rating: 5SY4650-6 is 50 A, while 5SY4304-7CV is a lower-rated variant. If the panel was wired for a lower current, the conductor sizing and upstream protection must be verified before substituting a 50 A breaker. The busbar comb and terminal spacing are identical.

What compliance documentation does Siemens provide for 5SY4650-6?

The part carries the standard SENTRON compliance package: CE marking for the European market, UL/CSA certification for North American acceptance, and RoHS/REACH declarations. The halogen-free and silicon-free construction supports clean-environment requirements. Specific declaration documents are available on request with the RFQ.