Its C-curve tripping characteristic means it handles inrush currents 5–10× the rated current without nuisance tripping — the right call for motor starters, contactor coils, and transformer primaries where the start-up surge is short but sharp. That 15 kA also holds for DC per IEC 60947-2, so it works on 60 V DC control buses up to 72 V max.
DIN-rail fit and wiring constraints