Siemens 5SY4602-5 — 4-Pole MCB (DIN Rail)

Siemens 5SY4602-5 SENTRON MCB, 4P, 2 A, Char A, 10/35 kA

MPN5SY4602-5
Active

Siemens SENTRON 5SY4602-5, 4-pole miniature circuit breaker, 2 A rated current, tripping characteristic A, 10 kA (EN 60898) / 35 kA (IEC 60947-2), 50/60 Hz, IP20, 4 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4602-5 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4602-5 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC2 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Voltage typeAC
5SY4602-5 — Protection
ParameterValue
Tripping characteristic (trip curve)A
Rated breaking capacity (Icn), per EN 6089810 kA
Rated breaking capacity, per IEC 60947-235 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY4602-5 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4602-5 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY4602-5 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

It is designed for branch-circuit protection in industrial control panels, suited for mechanical engineering and industry environments. Characteristic A trips between 2 and 3 times rated current, making it appropriate for protecting semiconductor loads or long cable runs where standard B or C curves might not coordinate.

Temperature derating and real-world current

The 2 A rating is at 35 °C ambient. At 40 °C the breaker carries 1.9 A, at 45 °C it is 1.85 A, at 50 °C it drops to 1.8 A, at 55 °C to 1.75 A, and at 60 °C to 1.7 A. If the panel runs warm — common in a densely packed enclosure — factor these numbers into the load calculation rather than relying on the 35 °C figure.

Frequently asked questions

How do I get current pricing and availability for 5SY4602-5?

Submit an RFQ through this listing; the part is sourced to order and availability with current pricing is confirmed at quote time.

What is 5SY4602-5's listed depth?

The overall depth is 76 mm, with an installation depth of 70 mm.

What is 5SY4602-5's tripping characteristic and breaking capacity?

It has tripping characteristic A (2–3× In) with a breaking capacity of 10 kA per EN 60898 and 35 kA per IEC 60947-2.

What compliance documentation is available for 5SY4602-5?

The breaker carries CE marking per the Low Voltage Directive; it is designed to EN 60898 and IEC 60947-2. The housing is halogen-free and silicon-free.