Skip to main content
Siemens 5SY4663-6 — 4-Pole MCB (DIN Rail)

Siemens 5SY4663-6 SENTRON MCB, 4-pole B-curve, 10 kA

MPN5SY4663-6
Active

Siemens SENTRON 5SY4663-6 miniature circuit breaker, 4-pole (3P+N), B-curve, 10 kA per EN 60898, 15 kA per IEC 60947-2, 400 V AC, 72 mm wide.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4663-6 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4663-6 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated voltage, AC (multi-phase)440 V
5SY4663-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
5SY4663-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4663-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY4663-6 — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)6 W

Product details

Integrator note — B-curve 4-pole MCB for mixed-load panels

It is a 4-pole (3P+N) unit, so the neutral pole switches with the phases, eliminating the need for a separate neutral disconnect in the panel. The dual standard means it can be specified under either the wiring-rule (EN 60898) or the industrial-equipment (IEC 60947-2) framework, depending on the local code. Rated operational voltage is 400 V AC (multi-phase) with a frequency of 50/60 Hz.

Width is 72 mm (4 modular units), depth 76 mm, height 90 mm, with an installation depth of 70 mm. The quick-assembly fastening method snaps onto standard DIN rail. Terminal design allows combined top and bottom entry, and the neutral conductor is switched internally — no external neutral bar needed. Halogen-free and silicon-free construction.

Environmental range and compliance

Operating temperature range -40 °C to 75 °C, with humidity derating: max 95% RH at 55 °C, 55% at 70 °C, 35% at 75 °C. Certified to IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 / CSA C22.2 No.235 (5 kA at 277 V AC per UL/CSA). Suitability marked for mechanical engineering and industry applications.

Frequently asked questions

How do I get current pricing and availability for 5SY4663-6?

We source and quote the 5SY4663-6 to order against an RFQ. Submit a request for current pricing and availability; confirmation is provided at quote time.

What is 5SY4663-6's listed depth (76 mm) on this component line?

The 5SY4663-6 has a depth of 76 mm, width 72 mm, height 90 mm, and an installation depth of 70 mm.

Will 5SY4663-6 drop into a panel that was specified around 5SY4140-7 without rewiring?

The 5SY4663-6 is a 4-pole (3P+N) B-curve MCB, while 5SY4140-7 is a different rating/pole configuration. Both share the SENTRON 5SY series footprint (72 mm width for 4-module units), so the mechanical fit on DIN rail is identical, but the electrical ratings differ — verify the BOM current and pole count before substituting.

What compliance documentation does this brand provide for 5SY4663-6 (RoHS, REACH, UL, IEC)?

The 5SY4663-6 carries certifications to IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 / CSA C22.2 No.235. It is halogen-free and silicon-free. RoHS and REACH compliance documentation is available from the manufacturer upon request.

MPN
5SY4663-6