The Siemens 5SY4663-8CC is a SENTRON miniature circuit breaker (MCB) rated 63 A with a D tripping characteristic, 4-pole configuration (3P+N), and a 10 kA breaking capacity per EN 60898 at 400 V AC.
Mounting, environment, and panel integration
Ambient operating range is -40 °C to 75 °C, but the thermal trip derates above 55 °C per the humidity/temperature influence table: max 95% RH at 55 °C, dropping to 35% RH at 75 °C. If the panel runs hot, factor that into the effective current rating.
Key electrical and mechanical parameters
Rated operational voltage is 400 V AC (440 V max for both single-phase and multi-phase operation). Frequency range is 50/60 Hz. Power loss per pole at rated current in hot state is 4.9 W — for a 4-pole breaker that's 19.6 W total heat to dissipate inside the enclosure; factor that into your thermal budget. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz.