Skip to main content
Siemens 5SY5108-7KK11 — 1-Pole MCB (DIN Rail)

Siemens 5SY5108-7KK11 SENTRON MCB, 1P C-curve 8 A, 10 kA

MPN5SY5108-7KK11

Siemens SENTRON 5SY5108-7KK11, miniature circuit breaker, 1-pole, C-curve, 8 A rated, 10 kA breaking capacity per EN 60898, railway design, halogen-free, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY5108-7KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityuniversal current
5SY5108-7KK11 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)10 kA
Energy limitation class3
Overvoltage categoryIII
5SY5108-7KK11 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY5108-7KK11 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Occupies 1 modular width (18 mm) on standard DIN rail, 76 mm depth, 90 mm height. Installation depth is 70 mm. Mounts in any position via the quick-assembly system — no tools needed for snap-on. Halogen-free and silicon-free construction matters in railway and process environments where outgassing can corrode contacts.

Thermal derating — the real-world rating

The 8 A rating holds at 35 °C ambient. Above that, derate linearly: 7.51 A at 40 °C, 7.26 A at 45 °C, 6.99 A at 50 °C, 6.72 A at 55 °C, and 6.43 A at 60 °C. If the panel runs hot — say 50 °C inside a sealed cabinet — you need to size the load at 7 A, not 8. The -40 °C to +75 °C operating range covers outdoor enclosures in cold climates.

Frequently asked questions

How do I get current pricing and availability for 5SY5108-7KK11?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time — no automated price or lead-time figure is published here.

What is 5SY5108-7KK11's listed depth (76 mm) on this component line?

The depth is 76 mm, width 18 mm (1 modular unit), height 90 mm. Installation depth is 70 mm. Mounts on standard DIN rail in any position.

Will 5SY5108-7KK11 drop into a panel specified around 5SY5250-7 without rewiring?

The 5SY5250-7 is a higher-current variant in the same SENTRON 5SY series — same 1-pole C-curve footprint, same DIN-rail mounting. It will physically fit the same panel position, but verify the load current matches the 8 A rating of this part; the 5SY5250-7 is rated higher and would need a different breaker for the same circuit.

What compliance documentation does this brand provide for 5SY5108-7KK11?

The part is designed to EN 60898 (AC breaking capacity 10 kA) and EN 60898-2 (DC breaking capacity 10 kA). It carries pollution degree 3 and overvoltage category III ratings. The manufacturer provides a declaration of conformity for CE marking; RoHS and REACH compliance documentation is available through the standard Siemens SENTRON documentation package.

MPN
5SY5108-7KK11