Skip to main content
Siemens 5SY5116-6KK11 — 1-Pole MCB (DIN Rail)

Siemens 5SY5116-6KK11 SENTRON MCB, 1P, 16 A, B Curve, 10 kA

MPN5SY5116-6KK11

Siemens SENTRON 5SY5116-6KK11, 1-pole miniature circuit breaker, 16 A rated current, B tripping characteristic, 10 kA breaking capacity per EN 60898, 15 kA per IEC 60947-2 at DC, 1 MW width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY5116-6KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityuniversal current
5SY5116-6KK11 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)10 kA
Energy limitation class3
Overvoltage categoryIII
5SY5116-6KK11 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY5116-6KK11 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Rated for ambient temperatures from -40 °C to +75 °C, with humidity derating: 95% RH up to 55 °C, 55% RH up to 70 °C, and 35% RH up to 75 °C. Overvoltage category III (fixed installation, distribution level). Vibration resistance per IEC 60068-2-6: ±1 mm at 5 to 25 Hz, 50 m/s² at 25 to 150 Hz — suitable for railway or mobile equipment applications. The product is designated for railway applications per its design code.

Frequently asked questions

What is the breaking capacity of the 5SY5116-6KK11?

10 kA per EN 60898 at AC, and 15 kA per IEC 60947-2 at DC. These are the maximum fault currents the breaker can safely interrupt under the respective standards.

Where can I buy the 5SY5116-6KK11?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will the 5SY5116-6KK11 drop into a panel specified around a 5SY3132-6 without rewiring?

Both are 1-pole SENTRON MCBs on a standard DIN rail, but the 5SY3132-6 is a C-curve variant. The physical footprint (1 MW, 18 mm width) and terminal arrangement are identical, so mechanical fit is the same. The difference is the tripping characteristic — B curve vs C curve — which affects coordination with downstream loads. No rewiring is needed for the breaker itself, but verify the curve matches the circuit's inrush requirements.

MPN
5SY5116-6KK11