Rated for ambient temperatures from -40 °C to +75 °C, with humidity derating: 95% RH up to 55 °C, 55% RH up to 70 °C, and 35% RH up to 75 °C. Overvoltage category III (fixed installation, distribution level). Vibration resistance per IEC 60068-2-6: ±1 mm at 5 to 25 Hz, 50 m/s² at 25 to 150 Hz — suitable for railway or mobile equipment applications. The product is designated for railway applications per its design code.
Siemens 5SY5116-6KK11 SENTRON MCB, 1P, 16 A, B Curve, 10 kA
Siemens SENTRON 5SY5116-6KK11, 1-pole miniature circuit breaker, 16 A rated current, B tripping characteristic, 10 kA breaking capacity per EN 60898, 15 kA per IEC 60947-2 at DC, 1 MW width, IP20.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Miniature circuit breaker |
| Brand name | SENTRON |
| Number of poles | 1 |
| Application suitability | universal current |
| Parameter | Value |
|---|---|
| Tripping characteristic class | B |
| Rated value (EN 60898) | 10 kA |
| Energy limitation class | 3 |
| Overvoltage category | III |
| Parameter | Value |
|---|---|
| Mounting position | any |
| Fastening method | Quick assembly system |
| Combined terminal, top | Yes |
| Combined terminal, bottom | Yes |
| Width | 18 mm |
| Height | 90 mm |
| Depth | 76 mm |
| Installation depth | 70 mm |
| Modular width units | 1 |
| Torque, min. | -40 °C |
| Torque, max. | 75 °C |
| Sealable | Yes |
| Parameter | Value |
|---|---|
| IP protection class | IP20, with connected conductors |
| Pollution degree | 3 |
| Halogen-free | Yes |
| Silicone-free | Yes |
Product details
Frequently asked questions
What is the breaking capacity of the 5SY5116-6KK11?
10 kA per EN 60898 at AC, and 15 kA per IEC 60947-2 at DC. These are the maximum fault currents the breaker can safely interrupt under the respective standards.
Where can I buy the 5SY5116-6KK11?
This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.
Will the 5SY5116-6KK11 drop into a panel specified around a 5SY3132-6 without rewiring?
Both are 1-pole SENTRON MCBs on a standard DIN rail, but the 5SY3132-6 is a C-curve variant. The physical footprint (1 MW, 18 mm width) and terminal arrangement are identical, so mechanical fit is the same. The difference is the tripping characteristic — B curve vs C curve — which affects coordination with downstream loads. No rewiring is needed for the breaker itself, but verify the curve matches the circuit's inrush requirements.