That dual-standard listing (IEC + UL) is the authority signal: the part is accepted in both European and North American panels, so a BOM freeze across jurisdictions holds on one order code. Single-pole design (1P) with no neutral switching — it breaks only the line conductor, which is the normal arrangement for a 120/240 V branch circuit where the neutral is bonded elsewhere.
Temperature derating — the real-world current
The 20 A rating holds at 35 °C ambient. Above that, the MCB derates: 18.78 A at 40 °C, 18.14 A at 45 °C, 17.48 A at 50 °C, 16.8 A at 55 °C, and 16.08 A at 60 °C.
Sealable terminals allow the installer to lock the cover after commissioning, meeting some site security requirements.