Skip to main content
Siemens 5SY5163-7KK11 — 1-Pole MCB (DIN Rail)

Siemens 5SY5163-7KK11 SENTRON MCB, 1P C 63A 10kA

MPN5SY5163-7KK11

Siemens SENTRON 5SY5163-7KK11, 1-pole miniature circuit breaker, C-curve 63 A, 10 kA breaking capacity per EN 60898, 1 MW width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY5163-7KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityuniversal current
5SY5163-7KK11 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SY5163-7KK11 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY5163-7KK11 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Siemens 5SY5163-7KK11 — 1-pole C-curve MCB at 63 A

The Siemens 5SY5163-7KK11 is a 1-pole SENTRON miniature circuit breaker with a C tripping characteristic, rated 63 A at AC and 220 V at DC. It delivers a 10 kA breaking capacity per EN 60898 and 10 kA at DC per EN 60898-2, making it suitable for general-purpose branch-circuit protection in distribution panels and control cabinets.

What the ratings mean for fit

The C-curve (tripping between 5 and 10 times rated current) is the standard choice for moderate inrush loads — motor starters, contactor coils, small transformers — where a B-curve would nuisance-trip on startup but a D-curve would delay too long for fault clearing. At 63 A, this MCB handles a 3-phase 22 kW motor or a single-phase 14 kW resistive load at 230 V, but the real-world current must be derated above 35 °C: 59.16 A at 40 °C, 55.06 A at 50 °C, and 50.65 A at 60 °C. In a warm panel (40 °C ambient), the continuous load should not exceed 59 A. Pollution degree 3 and overvoltage category III mean the breaker is rated for fixed installations inside an enclosure where conductive pollution may occur — typical for industrial control panels, not clean-room or sealed environments. The IP20 rating (with connected conductors) confirms it must be housed behind a panel door or cover.

Panel integration and mounting

Snaps onto DIN rail via the quick assembly system, occupying 1 modular width unit (18 mm). Installation depth is 70 mm; overall depth is 76 mm. Any mounting position is permitted. The combined terminal top and bottom accept conductors without special tools, and the touch-protection feature (fingertip-safe terminals) meets the requirements for live-work safety during commissioning.

Frequently asked questions

Where can I buy 5SY5163-7KK11 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is 5SY5163-7KK11's listed depth (76 mm) on this component line?

The overall depth is 76 mm, with an installation depth of 70 mm. It occupies 1 modular width unit (18 mm) and has a height of 90 mm.

What compliance documentation does this brand provide for 5SY5163-7KK11 (RoHS, REACH, UL, IEC)?

The breaker carries a 10 kA breaking capacity per EN 60898 and EN 60898-2, and is designed for overvoltage category III with pollution degree 3. It is halogen-free and silicon-free. For specific RoHS/REACH/UL declarations, the manufacturer's compliance documentation should be requested at quote time.

MPN
5SY5163-7KK11