Skip to main content
Siemens 5SY5205-7 — 2-Pole MCB (DIN Rail)

Siemens 5SY5205-7 SENTRON MCB, C-Curve 2-Pole, 10 kA

MPN5SY5205-7
Active

Siemens SENTRON 5SY5205-7 miniature circuit breaker, 2-pole, C-curve, 10 kA breaking capacity per IEC/EN 60898-2 and UL1077, 400 V AC / 440 V DC, 2 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY5205-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentuniversal current
5SY5205-7 — Electrical
ParameterValue
Number of poles2
5SY5205-7 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY5205-7 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY5205-7 — Environmental
ParameterValue
Pollution degree3
5SY5205-7 — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value10 kA
With single-phase operation at AC rated value440 V
Energy Limitation Class3

Product details

What it is and where it lands

The Siemens 5SY5205-7 is a 2-pole SENTRON miniature circuit breaker with a C tripping characteristic, rated for universal current (AC/DC) operation. It breaks 10 kA per IEC/EN 60898-2 and UL1077, and 15 kA per IEC 60947-2 at DC. That C-curve means it handles moderate inrush — common for motor starters, lighting banks, and small transformer loads — without nuisance tripping on startup, while still clearing a hard fault fast. It snaps onto a DIN rail (2 modular width units, 36 mm wide) and can mount in any position, so it fits tight panel layouts without derating.

Key ratings and what they mean for fit

Rated AC operating voltage is 400 V (single- or multi-phase) and DC is 440 V, with a maximum DC voltage of 500 V. The 10 kA breaking capacity at 400 V AC means it safely interrupts a fault current up to that level without welding contacts or cascading failure upstream — critical for panel coordination studies. At DC the IEC 60947-2 rating jumps to 15 kA, which matters for battery banks or DC bus protection where fault current can be stiffer. The breaker is rated for pollution degree 3 and overvoltage category III, so it's suited for industrial control panels, not just residential load centers. Ambient temperature range is -40 °C to 75 °C, with humidity derating above 55 °C — good for unheated enclosures or hot machine cabinets.

Frequently asked questions

Where can I buy 5SY5205-7 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

What compliance documentation does Siemens provide for 5SY5205-7?

The breaker is certified to IEC/EN 60898-2 and UL1077. It is halogen-free and silicon-free. Full RoHS and REACH declarations are available from Siemens upon request.

What is the breaking capacity of 5SY5205-7?

10 kA per IEC/EN 60898-2 and UL1077 at AC, and 15 kA per IEC 60947-2 at DC.

What is the tripping characteristic of 5SY5205-7?

C-curve — designed for moderate inrush currents typical of motor starters, lighting, and small transformers.

MPN
5SY5205-7