Skip to main content
Siemens 5SY5206-6CC — 2-Pole MCB (DIN Rail)

Siemens 5SY5206-6CC SENTRON MCB, 2P B 6A 440V DC 10kA

MPN5SY5206-6CC

Siemens SENTRON 5SY5206-6CC, miniature circuit breaker, 2-pole, B characteristic, 6 A at 35 °C, 440 V DC, 10 kA DC per IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY5206-6CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY5206-6CC — Electrical
ParameterValue
Number of poles2
5SY5206-6CC — Protection
ParameterValue
Tripping characteristic classB
Overvoltage categoryIII
5SY5206-6CC — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY5206-6CC — Environmental
ParameterValue
Pollution degree3

Product details

DC-rated miniature circuit breaker for industrial control panels

The Siemens 5SY5206-6CC is a 2-pole SENTRON miniature circuit breaker rated for 440 V DC with a 10 kA DC breaking capacity per IEC 60947-2. The B tripping characteristic (3–5× In) is specified for the DC circuit, so the magnetic trip thresholds are calibrated for DC fault profiles, not AC. The 6 A rating at 35 °C is the reference point; per the datasheet, the continuous current derates to 5.32 A at 40 °C, 4.95 A at 45 °C, 4.55 A at 50 °C, and 4.1 A at 55 °C — the thermal curve governs real-world panel loading, not the 35 °C number alone. The quick assembly system means it snaps onto the rail without tools.

Environmental and compliance profile

The sealable design allows the panel builder to lock the toggle position with a padlock or wire seal, preventing unauthorized switching during maintenance lockout procedures. Operating temperature range spans -40 °C to 75 °C, with humidity influence specified: max 95% RH up to 55 °C, derating to 55% RH at 70 °C and 35% RH at 75 °C. Vibration resistance per IEC 60068-2-6 is ±1 mm at 5 to 25 Hz and 50 m/s² at 25 to 150 Hz — suitable for installation on machinery or conveyors with moderate vibration profiles.

Frequently asked questions

How do I get current pricing and availability for 5SY5206-6CC?

The 5SY5206-6CC is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response.

What is 5SY5206-6CC's listed depth (76 mm) on this component line?

The overall depth is 76 mm, with an installation depth of 70 mm. The 6 mm difference accounts for the front projection of the toggle and terminal covers.

What is 5SY5206-6CC's listed width (36 mm) on this component line?

The width is 36 mm, which corresponds to 2 modular width units on a standard DIN-rail panel. This is the same footprint as the 5SY5240-7 and other 2-pole SENTRON 5SY breakers.

Will 5SY5206-6CC drop into a panel that was specified around 5SY5240-7 without rewiring?

Yes, it drops into the same DIN-rail slot — same 36 mm width, same 2 MW footprint, same terminal layout. No rewiring is needed. The only difference is the continuous current rating: 6 A at 35 °C for the 5SY5206-6CC versus a higher rating for the 5SY5240-7.

What compliance documentation does this brand provide for 5SY5206-6CC (RoHS, REACH, UL, IEC)?

The breaker is designed to IEC 60947-2 for DC breaking capacity (10 kA at 440 V DC) and carries the SENTRON brand from Siemens. The halogen-free and silicon-free construction supports RoHS and REACH compliance requirements. For specific UL listing or country-specific certification documents, the manufacturer's declaration package is available on request.

MPN
5SY5206-6CC