Skip to main content
Siemens 5SY5206-7KK11 — 2-Pole MCB (DIN Rail)

Siemens 5SY5206-7KK11 SENTRON MCB, 2P C-curve 6 A, 10 kA

MPN5SY5206-7KK11

Siemens SENTRON 5SY5206-7KK11 miniature circuit breaker, 2-pole, C-curve, rated 6 A AC, 10 kA breaking capacity, 2 MW width, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY5206-7KK11 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentuniversal current
5SY5206-7KK11 — Electrical
ParameterValue
Number of poles2
5SY5206-7KK11 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY5206-7KK11 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY5206-7KK11 — Environmental
ParameterValue
Pollution degree3
5SY5206-7KK11 — Specifications
ParameterValue
At AC rated value6 A
According to EN 60898 rated value10 kA
With single-phase operation at AC rated value440 V
Energy Limitation Class3

Product details

The Siemens SENTRON 5SY5206-7KK11 is a 2-pole miniature circuit breaker with C-curve tripping characteristic, rated 6 A at AC and carrying a 10 kA breaking capacity per EN 60898.

At 6 A it handles a 1.5 kW motor on 400 V three-phase or a lighting bank drawing 1.4 kW single-phase. Temperature derating is published: at 40 °C ambient the breaker carries 5.63 A, at 50 °C it drops to 5.24 A, and at 60 °C it's 4.82 A. If the panel runs hot — say inside a non-ventilated enclosure near a drive — size up one frame or the breaker nuisance-trips on a warm day. The 2-pole design switches both phase and neutral on single-phase circuits; neutral conductor switching is not fitted (: No), so it does not break the neutral on three-phase loads. For DC circuits, polarity must be observed.

The quick-assembly fastening system clips onto standard DIN rail. Installation depth is 70 mm — account for wiring space behind the rail. Sealable so the panel builder can lock the toggle position after commissioning.

Frequently asked questions

What is the breaking capacity of 5SY5206-7KK11?

10 kA per EN 60898 at AC, and 10 kA per EN 60898-2 at DC.

What is the temperature derating for this MCB?

At 40 °C it carries 5.63 A, at 50 °C it carries 5.24 A, and at 60 °C it carries 4.82 A.

Where can I buy 5SY5206-7KK11?

This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing.

MPN
5SY5206-7KK11