It's built to IEC / EN 60898-2 and UL1077 standards, so it's equally at home in a European panel or a North American machine that calls for UL-recognized branch protection.
The DC rating is 15 kA per IEC 60947-2, which is a step up; you'd see that in battery-bank or UPS circuits where fault current can run higher. The 440 V DC maximum operating voltage means it handles nominal 400 VDC strings without the arc-extinction worries a lower-rated DC breaker would have. Temperature range is -40 to 75 °C. Humidity derating: max 95% RH up to 55 °C, then decreasing to 35% at 75 °C.
Installation depth 70 mm, overall depth 76 mm.
Dual-listed to IEC/EN 60898-2 and UL1077 — that covers CE marking for European installations and UL recognition for North American machinery. Halogen-free and silicon-free construction is standard for SENTRON; it means no corrosive off-gassing if the breaker arcs, which matters in a sealed panel with sensitive electronics. Degree of pollution 3 and overvoltage category III confirm it's rated for the permanent wet, conductive-dust conditions you find in industrial environments — not just a clean electrical closet.